Electrical Calculators
Service / Load Calculation
Build a transparent preliminary connected-load worksheet.
01
Inputs
02
Result & worksheet
20375 VA · 84.9 A preliminary
Recorded summary
- General: 12000 VA
- Fixed equipment: 8000 VA
- Largest motor adder: 375 VA
- Preliminary total: 20375 VA
Formula used
Preliminary connected load = general + fixed equipment + 25% of largest motorCalculation steps
- 12000 + 8000 + (25% × 1500) = 20375 VA
- 20375 ÷ 240 = 84.9 A
Assumptions
- This is a preliminary connected-load worksheet, not a complete NEC service calculation
- Demand factors and required load categories are not applied
- Single-phase current is shown
Verify before use
- Applicable standard or optional calculation method
- Lighting, receptacle, appliance, HVAC, cooking, dryer, EV, and motor rules
- Existing loads and demand data where permitted
- Service equipment, utility, and local requirements