Electrical Calculators

Wire Ampacity / Wire Size

Document load, conductor material, and rating assumptions.

01

Inputs

02

Result & worksheet

36.4 A usable — below entered load

Recorded summary

  • Required ampacity: 50.0 A
  • Adjusted table ampacity: 36.4 A
  • Terminal limit: 40 A
  • Usable ampacity: 36.4 A

Formula used

Required ampacity = noncontinuous load + 125% of continuous load; adjusted ampacity = table ampacity × adjustment × correction

Calculation steps

  1. 20 A + (1.25 × 24 A) = 50.0 A required
  2. 50 A × 0.8 × 0.91 = 36.4 A adjusted
  3. Lower of adjusted ampacity and 40 A terminal limit = 36.4 A

Assumptions

  • Entered factors and temperature column are correct for the installation
  • No special cable, rooftop, bundling, dwelling, motor, transformer, or equipment rule supersedes this worksheet
  • The terminal limitation is entered separately

Verify before use

  • NEC Article 310 ampacity table and conditions of use
  • Temperature limitations at equipment terminations
  • Adjustment and ambient correction rules
  • Small-conductor, overcurrent-device, and equipment-specific rules
  • Voltage drop and local amendments