Troubleshooting

Contactor pulls in but motor does not run

Check line power, poles, overloads, conductors, and motor condition in sequence.

A closed control circuit does not prove that all three power poles, overload paths, conductors, and motor windings are intact.

01

Likely causes

  • Missing line power or open protective device.
  • Burned/open contactor pole.
  • Tripped or open overload.
  • Open conductor or motor winding.
02

Safe tests

  • De-energize and inspect poles, overloads, terminals, and continuity.
  • Verify control and power drawings match field wiring.
  • Use energized voltage tests only under an approved qualified-person procedure.
03

Expected evidence

  • All line phases present; all closed poles have low resistance; overload contacts are reset/closed; motor circuit continuity is consistent.
04

Correct & verify

  • Repair the proven open point, then verify acceleration, phase current balance, overload setting, and control stop functions.