Troubleshooting

Motor runs backwards

Verify equipment direction, phase sequence, wiring, and safe correction steps.

Confirm the required equipment direction before changing phase sequence or leads; reversing the wrong machine can create an immediate hazard.

01

Likely causes

  • Incoming phase sequence differs from expectation.
  • Motor or drive output leads were changed.
  • Drive direction command or parameter is inverted.
02

Safe tests

  • Stop and isolate the equipment; confirm the driven machine can be reversed safely.
  • Compare drawings, lead markings, phase sequence, and drive commands.
03

Corrective action

  • For an across-line three-phase motor, interchange two phases at the approved point.
  • For a VFD, follow drive/manufacturer direction logic; do not casually switch energized output leads.
04

Verification

  • Bump-test uncoupled or under an approved safe method, mark direction, and confirm process interlocks.